Connectivity Wizards
Check and update ATG connectivity with the Test Connectivity Wizard and Add/Change Connectivity Parameters Wizard.
The Test Connectivity Wizard and the Add/Change Connectivity Parameters Wizard are a pair of tools that work together to test and update ATG connectivity.
You may need to use these tools in the following scenarios:
- You've noticed data is not polling from the ATG correctly
- You've encountered an error sending/receiving messages using the ATG terminal emulator
- You're setting up a new facility or configuring a new ATG at an existing facility
- IT changes have been made at the facility that may impact ATG connectivity
Opening the Wizards
The path to access and use these tools can vary depending on the issue you're solving.
Open from the Compliance Dashboard
From the Compliance Dashboard, click on a Missing Inventory / Connectivity Issues alert item to open a detailed grid of relevant data. In the Default System View, the last column is Tools. When available, click Launch Connectivity Wizard in the Tools column.

Open from a Facility Page
From within a facility, click ATG Management in the left side menu, then click Connection. This will provide an overview of the facility's current connectivity mapping.
At the top right of the page, use the drop-down to select an option and click Go. The selection you make will determine whether the Test Connectivity Wizard or Add/Change Connectivity Parameters Wizard is opened first.

Open from the Global Menu
From anywhere in Titan Cloud, click the nine dots at the top right of the screen to open the global menu. Under Fuel Management, click on Test Connectivity Wizard.

Test Connectivity Wizard
This tool tests the ATG connectivity, and is usually (but not always) the first step when using the wizard tools.
Select Connectivity Type from the drop-down list. Depending on your selection, you will be prompted to provide applicable details.

Connectivity Type | Minimum Required Fields |
---|---|
Internet (Public IP)* | IP Address, Port |
VPN* | VPN, IP Address, Port |
Modem | Phone Number |
*If you're adding new IP/Port information for a Franklin Fueling gauge, Web Console Protocol and Port are also required.
What are my Web Console Protocol & Port?
Web protocols set the rules for how data is sent across networks.
By default, VR-450 and FF 200/400/600 gauges use https:// with port 443.
By default, FF 550s use http:// with port 80.
These defaults can be changed in the ATG itself.
Tip: We strongly recommend confirming these fields with your IT department or other internal source.
Additional fields, such as security code or password, may be required due to your setup.
Clicking Run Test will automatically send a series of commands to the ATG using the connection parameters provided.
At the conclusion of the test, you'll see a success or failure message, and the Add/Change Connectivity Parameters button will become available.
Test Failure
Depending on the reason for failure, some troubleshooting may be needed.
Test Success
If the test is successful, click the Add/Change Connectivity Parameters button to proceed to the next step.
Add/Change Connectivity Parameters Wizard
Depending on the path you took to open this wizard, you may be prompted to select or confirm the facility.
Then, use the drop-down menus to specify the ATG mapping and click Continue.

Tip: Unless you are setting up a new facility, you should always be selecting “Update existing site” in the first drop-down menu.
Confirm the details on the next screen, and if everything is correct, click Confirm.

Please give the system up to 15 minutes to update the ATG connectivity parameters.
Once everything is updated, you will see the changes on the Facility Profile page under the ATG Information tab.

Note: The ATG Connection information on the Facility Profile has an IP Address field and a Polling IP Address field.
The IP Address field is editable from this screen but does not impact ATG polling. The Polling IP Address field can only be updated using the Connectivity Wizards.